The feed water container used for the storage of feed water. In the feed water container, the feed water
for the thermal degassing are heated and mixed with the dosing.
The volume of the feed water container should be at least 50% of the installed steam power per hour.
This is important among other things, to provide sufficient residence time for degassing the water and
binding to the dosing means.
Uneven condensate return or a large volume of steam network, the volume of feed water container
should be correspondingly higher.